Description:
Flexible, flame-retarded VW-1, dual wall heat-shrink polyolefin tubing, UL/CSA recognized. High shrink ratio for sealed insulation of splices, terminations and wire harness branches.
Shrink ratio: 3:1
Materials: Crosslinked EVA
Installation temperature:
- Shrinking temperature: > 100°C
- Operating temperature: -55°C to +110°C 1)
Features and benefits
- UL Recognized Component (US & Canada)
- 3:1 ratio - fits parts 3x larger than the cable
- Adhesive lining seals against moisture
- Highly flame retarded VW-1 2)
- Fast installation with heat guns
- Remains flexible after recovery
- 600V insulation rating
1) Outer wall operating temperature -55°C to +135°C
2) Black color only
Download:
NFD301 | Supplementary safety information
Standard packaging:
Reel,
Dispenser box,
Meter length
Related products:
NFD401,
NFD-HT301,
NFD-HT401,
HAG,
CHAG
Tags

| DIMENSIONS | ||||
|---|---|---|---|---|
| Size | Min. Ø supplied "D" [mm] | Max. Ø recovered "d" [mm] | Recovered wall thickness [NOM] "W" [mm] | Min, concentricity expanded [%] |
| [mm] | ||||
| 3,0 | 3,0 | 1,0 | 1,00 | 60 |
| 4,8 |
4,8 | 1,5 | 1,00 | 60 |
| 6,0 | 6,0 | 2,0 | 1,10 | 60 |
| 9,0 | 9,0 | 3,0 | 1,30 | 60 |
| 12,0 | 12,0 | 4,0 | 1,70 | 60 |
| 18,0 | 18,0 | 6,0 | 2,00 | 60 |
| 24,0 | 24,0 | 8,0 | 2,50 | 60 |
| 39,0 | 39,0 | 13,0 | 2,50 | 60 |
Physical properties:
| Description | Test method | Requirements | Test results |
|---|---|---|---|
| Dimensional | EN IEC 60684-2 | in-house | pass |
| Dimensional stability on storage | in-house | pass | |
| Tensile strength | min. 9MPa | 20MPa | |
| Elongation at break | min. 200% | 440% | |
| Secant modulus at 2% | 40-175MPa | 100MPa | |
| Longitudinal change | -15 to +1% | pass | |
| Restricted shrinkage | no cracking or splitting | pass | |
| Water absorption | max. 1% | 0,23% | |
| Density | - | 1,10 |
Thermal properties:
| Description | Test method | Requirements | Test results |
|---|---|---|---|
| Heat shock 4h at 200°C | EN IEC 60684-2 | - | - |
| - Tensile strength | min. 7MPa | 16MPa | |
| - Elongation at break | min. 150% | 443% | |
| Heat ageing 168h at 150°C | - | - | |
| - Tensile strength | min. 7MPa | 15MPa | |
| - Elongation at break | min. 150% | 425% | |
| Bending at low temp. -55°C | no cracking shall be visible | pass |
Fire properties:
| Description | Test method | Requirements | Test results |
|---|---|---|---|
| Vertical flammability - flame test | UL224 pt. 5.11 |
time of burning ≤60s; the indicator flag shall not be damaged more than 25%; no ignition of the cotton |
pass 3) |
| Vertical flammability - VW-1 | UL224 pt. 5.12 |
time of burning ≤60s; the indicator flag shall not be damaged more than 25%; no ignition of the cotton |
pass 2) |
Chemical properties:
| Description | Test method | Requirements | Test results |
|---|---|---|---|
| Resistance to selected fluids | EN IEC 60684-2 | EN 60684-3-248 tab. 7 | pass Tested fluids: ISO1817 liquids B, F, 101, 103 and oil no. 2; S-1714; H-520; O-1176; O-142; Cleaning fluids; Runway de-icers; Aircraft de-icers |
| - Tensile strength | min. 7MPa | ||
| - Elongation at break | min. 200% | ||
| Color fastness to light | fastness standard 5 | pass |
Physicochemical properties:
| Description | Test method | Requirements | Test results |
|---|---|---|---|
| 1000 h UV resistance, (8 h UV / 4 h condensation) | ASTM G154 | min. 50% of non-aged physical properties | pass |
| - Tensile strength | |||
| - Elongation at break | |||
| Fungus resistance | EN IEC 60684-2 | - | - |
| - Tensile strength | min. 7MPA | 15MPa | |
| - Elongation at break | min. 200% | 440% |
Electrical properties:
| Description | Test method | Requirements | Test results |
|---|---|---|---|
| Breakdown voltage | EN IEC 60684-2 | min. 25kV | 37kV |
| Volume resistivity at room temp. | min. 1011Ωm | 2,0*1012Ωm | |
| Voltage rating | UL224 | 600V | 600V |
Note: Unless otherwise stated, all values are determined in accordance with EN IEC 60684-2. The measured characteristics correspond to properties commonly evaluated under ASTM D2671.
2) Black color only
3) Recovered ID up to 13.0 mm. All colors except clear
Certification:
UL224 / CSA C22.2 No. 198.1 File E228117, 125°C, 600V 3)
3) Recovered ID up to 13.0 mm. All colors except clear
Approval:
- Complies with REACH and RoHS

Description:
Flexible, flame-retarded VW-1, dual wall heat-shrink polyolefin tubing, UL/CSA recognized. High shrink ratio for sealed insulation of splices, terminations and wire harness branches.
Shrink ratio: 4:1
Materials: Crosslinked EVA
Installation temperature:
- Shrinking temperature: > 100°C
- Operating temperature: -55°C to +110°C 1)
Features and benefits
- UL Recognized Component (US & Canada)
- 4:1 ratio - fits parts 4x larger than the cable
- Adhesive lining seals against moisture
- Highly flame retarded VW-1 2)
- Fast installation with heat guns
- Remains flexible after recovery
- 600V insulation rating
1) Outer wall operating temperature -55°C to +135°C
2) Black color only
Download:
NFD401 | Supplementary safety information
Standard packaging:
Reel,
Dispenser box,
Meter length
Related products:
NFD301,
NFD-HT301,
NFD-HT401,
HAG,
CHAG
Tags

| DIMENSIONS | ||||
|---|---|---|---|---|
| Size | Min. Ø supplied "D" [mm] | Max. Ø recovered "d" [mm] | Recovered wall thickness [NOM] "W" [mm] | Min, concentricity expanded [%] |
| [mm] | ||||
| 4,0 | 4,0 | 1,0 | 1,00 | 60 |
| 8,0 |
8,0 | 2,0 | 1,00 | 60 |
| 12,0 | 12,0 | 3,0 | 1,30 | 60 |
| 16,0 | 16,0 | 4,0 | 1,80 | 60 |
| 24,0 | 24,0 | 6,0 | 1,80 | 60 |
| 32,0 | 32,0 | 8,0 | 2,50 | 60 |
| 52,0 | 52,0 | 13,0 | 2,90 | 60 |
Physical properties:
| Description | Test method | Requirements | Test results |
|---|---|---|---|
| Dimensional | EN IEC 60684-2 | in-house | pass |
| Dimensional stability on storage | in-house | pass | |
| Tensile strength | min. 9MPa | 22MPa | |
| Elongation at break | min. 200% | 460% | |
| Secant modulus at 2% | 40-175MPa | 125MPa | |
| Longitudinal change | -15 to +1% | pass | |
| Restricted shrinkage | no cracking or splitting | pass | |
| Water absorption | max. 1% | 0,32% | |
| Density | - | 1,10 |
Thermal properties:
| Description | Test method | Requirements | Test results |
|---|---|---|---|
| Heat shock 4h at 200°C | EN IEC 60684-2 | - | - |
| - Tensile strength | min. 7MPa | 19MPa | |
| - Elongation at break | min. 150% | 460% | |
| Heat ageing 168h at 150°C | - | - | |
| - Tensile strength | min. 7MPa | 16MPa | |
| - Elongation at break | min. 150% | 449% | |
| Bending at low temp. -55°C | no cracking shall be visible | pass |
Fire properties:
| Description | Test method | Requirements | Test results |
|---|---|---|---|
| Vertical flammability - flame test | UL224 pt. 5.11 |
time of burning ≤60s; the indicator flag shall not be damaged more than 25%; no ignition of the cotton |
pass 3) |
| Vertical flammability - VW-1 | UL224 pt. 5.12 |
time of burning ≤60s; the indicator flag shall not be damaged more than 25%; no ignition of the cotton |
pass 2) |
Chemical properties:
| Description | Test method | Requirements | Test results |
|---|---|---|---|
| Resistance to selected fluids | EN IEC 60684-2 | EN 60684-3-248 tab. 7 | pass Tested fluids: ISO1817 liquids B, F, 101, 103 and oil no. 2; S-1714; H-520; O-1176; O-142; Cleaning fluids; Runway de-icers; Aircraft de-icers |
| - Tensile strength | min. 7MPa | ||
| - Elongation at break | min. 200% | ||
| Color fastness to light | fastness standard 5 | pass |
Physicochemical properties:
| Description | Test method | Requirements | Test results |
|---|---|---|---|
| 1000 h UV resistance, (8 h UV / 4 h condensation) | ASTM G154 | min. 50% of non-aged physical properties | pass |
| - Tensile strength | |||
| - Elongation at break | |||
| Fungus resistance | EN IEC 60684-2 | - | - |
| - Tensile strength | min. 7MPA | 15MPa | |
| - Elongation at break | min. 200% | 440% |
Electrical properties:
| Description | Test method | Requirements | Test results |
|---|---|---|---|
| Breakdown voltage | EN IEC 60684-2 | min. 25kV | 42kV |
| Volume resistivity at room temp. | min. 1011Ωm | 1,6*1012Ωm | |
| Voltage rating | UL224 | 600V | 600V |
Note: Unless otherwise stated, all values are determined in accordance with EN IEC 60684-2. The measured characteristics correspond to properties commonly evaluated under ASTM D2671.
2) Black color only
3) Recovered ID up to 13.0 mm. All colors except clear
Certification:
UL224 / CSA C22.2 No. 198.1 File E228117, 125°C, 600V 3)
3) Recovered ID up to 13.0 mm. All colors except clear
Approval:
- Complies with REACH and RoHS

Description:
High temperature resistant, dual wall, flexible heat shrink polyolefin tubing. The polyamide hot set adhesive melts and flows during the shrinkage to seal and encapsulate the inner components. The excellent adhesion against several medium, guarantees a strong protection.
Features:
- Operating temperature -55°C to +125°C
- Polyamide adhesive lined
- Shrink ratio 3:1 and 4:1
- Excellent adherence to steel, plastics & other materials
- Shrink temperature > 100°C
- Very flexible.
Download:
NFD HT | Supplementary safety information
Standard packaging:
Meter lengths,
Reels
| Size [mm] | Minimum Inside Diameter Supplied [mm] | Maximum Inside Diameter Recovered [mm] | Wall Thickness Recovered [nominal value, mm] |
|---|---|---|---|
| 3/1 | 3,0 | 1,0 | 1,0 |
| 4/1 | 4,0 | 1,0 | 1,02 |
| 4,8/1,5 | 4,8 | 1,5 | 1,0 |
| 6/2 | 6,0 | 2,0 | 1,1 |
| 8/2 | 8,0 | 2,0 | 1,02 |
| 9/3 | 9,0 | 3,0 | 1,3 |
| 12/3 | 12,0 | 3,0 | 1,3 |
| 12/4 | 12,0 | 4,0 | 1,7 |
| 16/4 | 16,0 | 4,0 | 1,78 |
| 18/6 | 18,0 | 6,0 | 2,0 |
| 24/6 | 24,0 | 6,0 | 2,1 |
| 24/8 | 24,0 | 8,0 | 2,5 |
| 32/8 | 32,0 | 8,0 | 2,5 |
| 39/13 | 39,0 | 13,0 | 2,5 |
Physical properties:
| Property | Test method | Typical value |
|---|---|---|
| Tensile strength | EN 60684-2-19 | 15 MPa |
| Elongation at break | EN 60684-2-19 | 500% |
| Longitudinal change | EN 60684-2-9 | -15% to +1% |
| Water absorption | EN 60684-2-40 | ≤0,5% |
| Specific gravity | EN 60684-2-4 | 1.16 |
Thermal properties:
Elongation at break: 450%
| Property | Test method | Typical value |
|---|---|---|
| Heat shock 4 hours at 200°C | EN 60684-2-6 | no dripping, cracking or flowing |
| Tensile strength: 12 MPa | ||
| Elongation at break: 480% | ||
| Heat aging 168 hours at 150°C | EN 60684-2-39 | Tensile strength: 15 MPa |
| Elongation at break: 450% | ||
| Low temp. flexibility at -55°C | EN 60684-2-14 | no cracking |
| Flammability | EN 60684-2-26 | method A pass |
Electrical properties:
| Property | Test method | Typical value |
|---|---|---|
| Breakdown voltage | EN 60684-2-21 | 15kV/mm |
| Volume resistivity | EN 60684-2-23 | 1014 ohm/cm |
Adhesive properties:
| Property | Test method | Typical value |
|---|---|---|
| Peel strength | EN 60684-2-54 |
PE: 147 N/25mm |
| Steel: 157 N/25mm | ||
| Aluminium: 200 N/25mm | ||
| Copper: 135 N/25mm | ||
| Elevated temp. performance (125°C) | EN 60684-3-248 | 0,73 mm |